ANALISIS KINERJA SISTEM KELISTRIKAN FAKULTAS HUKUM UNIVERSITAS LANCANG KUNING PEKANBARU

Tags:

Publication Type:

Journal Article

Source:

jurnal teknologi, Volume 8, Number 1 (2015)

Keywords:

earthing system, electrical energy, load current, power loss

Abstract:

Electricity supply stable and continuous is a necessary condition that must be fulfilled to meet the electricity needs. Electrical energy is dangerous for human use and the environment, so that the electrical utility of a building should be safe. Faculty of Law, University of Lancang Kuning is an educational institution that has several departments that have administration and teaching and learning activities using electrical appliances. The use of electrical loads are also widely used in the installation of lighting and other electrical equipment.
The purpose of this study was carried out to analyze and calculate the flow on each - each phase on the electrical system, calculate and evaluate the use of load imbalance conductor wires contained in the electrical system of the Faculty of Law Unilak. Based on the results of the discussion of the results of the calculations showed that the use of the current load on the first building large load current 8.22 amperes, building II and building III 10.24 1.57 ampere ampere. While the power loss in the first building at 35.61 watts, building II 55.26 watts and 1.31 watts building III. To sisitem great earthing earthing resistance value in the building I 59, 5 ohms, 178 ohms building II and 119 ohms building III.

AttachmentSize
75-82_tanjung.pdf411.28 KB